Description
Liebert GXT5
The Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. The new Liebert® GXT5™ from Vertiv™ is an advanced version of the widely-regarded GXT UPS Series. GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications.
- Banking, Financial and Insurance
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Manufacturing
- Retail and Wholesale
- Telecom
- Transportation
Features
STANDARD SPECS
Ratings (VA /W). 750 VA / 750 W
Dimensions and Weight
Dimensions (mm) Unit, W×D×H 400×430×85
Unit Weight (kg) 16.5
Input
Rated Volatge 230 VAC
Rated Frequency 50 Hz / 60 Hz
Frequency Range 40 to 70 Hz
Power Factor ≥0.99
Input Power Cord C14
Output
Nominal Voltage 200/208/220/230/240 VAC
Waveform Sine wave
Inverter Overload Capability >200% minimum 250 ms, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds
Efficiency in Online Mode Up to 93%
Active Eco Mode Up to 98%
Output Receptacles (8) EN60320/C13
Internal Battery
Rated Voltage 36 Vdc
Charger Current Nominal 2.2 A; Maximum 8 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 3 x 12 V x 9.0 Ah
End Cell Voltage 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, canbe selected by PARAMSET)
Floating Voltage Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range 30 Vdc to 42.3 Vdc
General
Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Relative Humidity 0 to 95% non-condensing
Operating Elevation Up to 3,000 m at 25°C without derating
Audible Noise <46 dBA max @ 3 ft. (1 m) front and sides <43 dBA max @ 3 ft. (1 m) rear
Safety UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
Transportation ISTA Procedure 1A
Surge Immunity : ANSI C62.41 Category B