Description
MEMOPOWER Plus II
MEMOPOWER-Ⅲ 6-10KVA
6kVA-10kVA
• Optimization battery group, the quantity of battery: 16/18/20pcs (Settable)
• Wide input voltage range:110~286Vac
• Input power factor 0.99 with PFC
• Wide input frequency range
• Selectable output voltage: 208/220/230/240Vac
• Generator compatible
• ECO mode operation for energy saving
• Self-testing when UPS startup
• Multiple communication interface:RS232/USB/EPO(Relay card /SNMP card optional)
• Cold start
• Design with maintenance switch (Optional)
• Intelligent fan speed regulation
• Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm
Technical Specification
Technical Specification
Model MP 6k S
Capacity 6000VA/ 5400W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Bypass voltage range Max.voltage:230~264Vac
Min.voltage:176~220Vac
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output frequency Line Mode ±10% of the rated frequency
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THDv) ≤2% Linear load
≤5% Non linear load
Transfer time
AC mode to Bat.Mode 0ms
Inverter to Bypass 5ms (Typical)
Output waveform Pure Sinewave
Overload
Line Mode Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately
Bypass Mode 40A (Breaker)
Efficiency 93.50%
BATTERY
Battery voltage 240Vdc
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max. current 8A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage,
Battery voltage, Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continuously beeping
PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337 ; S:191 x 460 x 720 (With wheel)
Net weight (kg) 69.5
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m, derating required when>1500m
Noise level <55db at 1 Meter <58db at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8