Description
Professional Series II+ (1P/1P) – Rack/Tower
Prolink Professional II+ Series (1P/1P) Rack/Tower is a single-phase UPS system using microprocessor-controlled true online double conversion technology and it can be used to provide protection for critical loads, especially on IT applications. High input power factor correction in the system improves efficiency and reduces overall losses.
- Model PRO902-ERS / Railkit for data rack cabinet additional cost.
- Warranty 2 Years / 1 Year Battery
At a glance
True double-conversion
Microprocessor control
Input power factor correction
Smart SNMP
Converter mode (optional)
Output power factor 0.8
True double conversion online technology
Smoothed out power fluctuations so that there would be less damage to downtime issues that could cost millions.
Generator compatible
Works with a generator as a power source and converts perfect power to the connected loads.
LCD display
Useful information such as battery health and power conditions are shown at a glance through the LCD display.
Emergency Power Off function
Safety feature that will immediately disconnect the UPS loads from utility power in the event of an emergency to ensure there’s no risk of electrical shock when fire extinguishers or sprinklers are set off inside the room.
(Optional for 1~3kVA, built-in for 6 – 10kVA)
SPECIFICATIONS
GENERAL
UPS Type | Rack / Tower |
Phase | Single phase with ground |
Rating (VA) | 2000 |
Nominal Power (W) | 1800 |
Standard ModelDimension (mm) | 410 x 438 x 88 [2U] (D x W x H) |
Weight (kg) | 19 |
Long-run ModelDimension (mm) | 410 x 438 x 88 [2U] (D x W x H) |
Weight (kg) | 12 |
INPUT
Connection Type | IEC 320-C14 |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC (Load at 50%)160-280 VAC (Load at 100%) |
Frequency Range | 40 ~ 70 Hz |
Power Factor | ≥ 0.99 |
OUTPUT
Connection Type | Standard Model
Long-Run Model
|
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 47 ~ 53 Hz or 57 ~ 63 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≤3% THD (Linear load)≤6% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*USB Port |
BATTERY
Standard ModelType | 12V / 9Ah |
Numbers | 4 |
Typical Recharge Time | 4 hours recovery to 90% capacity |
Long-run ModelType | Depending on the capacity of external batteries |
Number | 6 |
Charging Current (max) | 1A / 2A / 4A / 6A Adjustable |
REAR PANEL
1. AC Input2. Input circuit breaker
3. USB Communication port 4. RS-232 communication port 5. Intelligent slot 6. External battery connection (Only available for L model) 7. Output receptacles (IEC C13) 8. Output receptacles (Universal outlet) |
Reviews
There are no reviews yet.