Description
N Series UPS, Single Phase, 6/10 kVA
Innovative. Compact. High Performance.
The Amplon N series 6-10kVA UPS is a single-phase on-line UPS with pioneering technology that provides output power factor up to unity and AC-AC efficiency to a maximum of 95%. Its remarkably compact dimensions reserve more room for critical equipment such as workstations, POSs, ATMs, office appliances, small server rooms, and production equipment. The Amplon N series’ superior features include an N+X parallel redundancy function and variable fan speed control to guarantee high system availability and the best Total Cost of Ownership (TCO).
Applications
The Most Compact Design and Best TCO
The smallest dimensions in its class save significant space for more critical equipment.
A pioneer in unity power factor (kVA=kW) to maximize power availability.
The highest AC-AC efficiency of up to 95% and efficiency of 98% in ECO mode for exceptional energy cost savings.
Automatic speed regulation function with multi-stage fan speed control maximizes system efficiency, significantly reduces audible noise, and prolongs the service life of the fans.
High Availability
True online double-conversion topology and zero transfer time to battery ensure high reliability.
Parallel configuration for expansion and N+X redundancy up to 4 units.
Advanced DSP (Digital Signal Processor) controller for fast computation capabilities and a simplified control circuit for enhanced stability.
Generator compatibility ensures continuous and reliable power.
Intelligent Management
Excellent local communications through user-friendly LCD display and LED indicators.
Intelligent battery management maximizes battery performance and extends battery life.
Various types of communication interfaces enhance monitoring and manageability.
ModelN-6K / N-10K
Power Rating:
● N-6K6 kVA / 6 KW
● N-10K10 kVA / 10 KW
Input
Nominal Voltage200/208/220/230/240 Vac
Voltage Range200/208 (de-rating to 90%): 100~280 Vac *
220/230/240: 100~280 Vac **
Frequency40~70 Hz
Power Factor> 0.99 (full load)
Current Harmonic Distortion< 3%
Output
Power Factor1
Nominal Voltage200/208/220/230/240 Vac
Frequency50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion< 2% (linear load)
Overload Capability< 105%: Continuous
105~125%: 2 minutes
125~150%: 30 seconds
Crest Factor3:1
Efficiency
AC-ACUp to 95%
ECO mode up to 98%
Battery
Voltage192-264 Vdc adjustable
Charge Current1.5-8 A selectable
Audible Noise< 50 dBA
DisplayLED indicators and LCD display
Communication InterfacesREPO x 1, RS-232 Port x 1, USB Port x 1, Parallel Port x 2, Smart Slot x 1
Physical
Dimensions (W x D x H)190 x 390 x 325 mm
Weight:
● N-6K10.1 kg
● N-10K12.7 kg
Environment
Operating Altitude1000 meters (without de-rating)
Operating Temperature0~40℃ (at 100% load)
45~55℃ (de-rating to 80%)
Storage Temperature-15~50℃
Relative Humidity5~95% (non-condensing)
* Linear de-rating between 40~90% load at 100~175 Vac.
** Linear de-rating between 40~100% load at 100~194 Vac.
All specifications are subject to change without prior notice.