Eaton DXRT 10KVA 10kW 230V, Tower/Rackmount 5U Online Ups Single Phase

251,000.00

Category: Tags: , , , , , , , , , ,

Description

DX RT UPS

Uninterruptible power systems (UPS) protect sensitive electronic equipment from the most common power problems, including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching transients, and harmonic distortion.   Power outages may occur unexpectedly, and the power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware -causing hours of lost productivity and expensive repairs.

The Eaton DX-RT 6-10kW is a true online double conversion rack and tower convertible UPS system that affordably provides robust, reliable, compact and efficient power management solution for mission critical applications from downtime and data-loss.

The Eaton DX-RT 6-10kW UPS provides true Output Unity PF 1 (VA=Watts)  When power factor is at unity (1), the voltage and current waves are aligned or in phase with one another, thus helping to eliminate costly utility charges.

Applications: IT, Storage, Networking and Server equipment, telecommunications and VoIP equipment, small and Micro Data Centre application, bio-Metrics, radiology and medical equipment, laboratory equipment and precision instruments, banking and security systems, manufacturing.

 

_______________________

Manageability

Get clear information on the UPS’ measurements and status with the graphical LCD display
Up to 100 event log can be read through LCD
Easily communicate with the UPS through USB, RS232 serial, EPO, programmable dry in/ dry out or over the network with the optional network cards Network-M2/ INDGW-M2/ Relay-MS cards.
Equipped with Eaton’s Intelligent Power™ Software for seamless integration with all major OS and virtualization platforms.
_________________

Flexibility

Adjustable charger current and set the most suitable charger current in a range of 0 to 12 Amps
Meet the long backup time requirement with flexible battery configuration of 16-20 pcs battery configuration
Extend runtime with configurable 3U standard battery module or third-party battery pack
Suitable for most installations with tower or rack standard 19-inch cabinet
__________________________________________

Intelligent Power Manager

 

The power of automation allows you to make tasks simpler via advanced alerts and automated resolution

DX RT UPS Models & Specifications

TECHNICAL SPECIFICATIONS

DXRT 10Ki
Rating (VA/W) 10KVA/10KW
Format Tower / Rack
Input Characteristics
Input voltage range 110VAC~275VAC
Input frequency range 40~70Hz
Power factor ≥ 0.995
Harmonic (linear load) <3%
Output Characteristics
Power factor 1
Output voltage 208 / 220 / 230 / 240VAC (default 220VAC)
Voltage variation ±1%
Output frequency (battery mode) (50/60±0.1)Hz
Voltage distortion (linear load) <1%
Overload capacity 105%~125% for 10 minutes; 125%~150% for 30 seconds

Battery Characteristics
Type Valve-controlled maintenance-free lead-acid type

Battery voltage 16pcs default
Backup time – Full load/ 50% load 2 minutes / 8 minutes

(PF=0.9)
Charger current 0~4A (default 2A)
UPS Characteristics
Efficiency double conversion mode 95%; ECO mode 98%
Maintenance bypass switch Built-in

Dimensions W x D x H / Weight
Dimensions (mm) 443 x 570 x 87
EBM 443 x 593 x 129

Weight (kg) 14.5
EBM 45.5Operating conditions, Standards and Approvals
Display Graphical LCD + LED indicator
Operating temperature 0 to 40°C
Humidity 0 ~ 95% (no condensation)
Altitude <1000m no derating, >1000m derating 1% for every 100m
Storage temperature -20 to 55°C (without battery)
Protection level IP20
Parallel Support 3 units
Communication RS232 / USB / Network-M2/ INDGW-M2/ Relay-MS cards
Options Rack mounting rail, EBM, PDU, centralized monitoring software IPM, parallel kit
Approvals CE