Description
GH11 Pro 6K-10KVA Parallel
GH11 Pro is double-conversion high frequency online UPS with a output power factor 1.0 Ranging from 6KVA to 10KVA, It’s design in small footprints with DSP technology and active input power factor correction design to ensure better output voltage conditions, power quality and power performance at all times. Its dual mains inputs will secure the power reliability in power fluctuation area.
- True double-conversion
- DSP technology guarantees high performance
- Output power factor 1
- Wide input voltage range (110-300 VAC)
- High efficiency up to 94%
- Active input power factor correction 0.99
- 50Hz/60Hz frequency converter mode
- Emergency power off function (EPO)
- ECO mode for energy saving
- Generator compatible
- SNMP/USB/RS-232 communications
- Adjustable battery numbers
- Optional Maintenance bypass available
- Optional N+X parallel redundancy
- Optional OVCD protection
TECH SPECS
Model GHII Pro- 6K(L)
PHASE 1 phase in / 1 phase out
CAPACITY 6000VA /6000W
INPUT
Nominal Voltage 208/220/230/240 VAC
Input Voltage Range 110-300VAC ± 3 0/0 at 50% load 176-300VAC ± 3 0/0 at 100% load
Frequency Range 46-54 Hz or 56-64 Hz
Phase Angle 0.99 a full load
Power Factor <4 0/0 Load,
OUTPUT
Output Voltage 208*/220/230/240 VAC
Frequency Range (Synchronized Range) (Batt. Mode) 46-54 Hz or 56-64 Hz
Frequency Range Current Crest Ratio 50 ± 0.1 Hz or 60 Hz ± O.1 Hz
(max.)
Harmonic Distortion % T HD (Linear Load), 4 % T HD (Non-linear Load)
Transfer Time
AC to DC Zero
Inverter to Bypass Zero
Waveform (Batt. Mode) Pure Sinewave
Overload
AC Mode 100%-110%: 10 min : 110% -130% : 1min : 1 sec
Battery Mode 100%-110%: 30 sec : 110% -130% : 10 sec : 1 sec
EFFICIENCY
AC Mode 94%
Battery Mode 91 %
BATTERY
Standard
Model
Battery Type 12 V/ 7 AH
Numbers 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (max.) 1.0 A
Charging Voltage 218.4 VOC ± 1%
Standard
Model
Dimension, DxWxH (mm) 369 x 190 x 688
Net Weight (kgs) 54
Dimension, DxWxH (mm)
Reviews