Description
GP800 is a transformer-based UPS of KSTAR, both input and output are single phase, the output power factor is 0.8. This series UPS is high reliable and have good impact resistance, it can suppply safe and reliable protection for load.
● High reliability double conversion design,pure sine wave
● Strong protection for load:Built-in isolation transformer,strong anti-interference ability
● Wide input range:165~275Vac
● Optimization of high-performance battery
● Battery cold start function
● Comprehensive and reliable protection
● User-friendly network management
Technical Specification
MODEL 10kVA/8kW
INPUT
Nominal Voltage 220/230Vac
Operating Voltage
Range 165~275Vac
Operating
Frequency
Range 50/60Hz (±5%)
Power Factor >0.97 (with filter)
OUTPUT
Output Voltage 220Vac(±0.5%) / 230Vac(±0.5%)
Output frequency 50/60Hz(±0.5%)
Crest factor 3:1 (max)
Efficiency >88%
EFFICIENCY
AC Mode 89%
Battery Mode 85%
BATTERY
Battery voltage 192Vdc
SYSTEM FEATURES
Transfer time 0 ms ( Line mode→ Battery mode)
Overload >125% : 1min, >150%: 200ms
Communication
interface RS232, SNMP(optional), Dry contact (optional)
ENVIRONMENT
Operating
Temperature 0℃~40℃
Storage
temperature -25~55℃
Humidity range 0~95% (non-condensing)
Altitude <1500m
Noise level <55dB
PHYSICAL
Dimension
W×D×H (mm)230×580×720
Net Weight 82
STANDARDS
Safety IEC/EN62040-1; IEC/EN60950-1
EMC IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8
Warranty 2 Years / 1 Year Battery
Reviews
There are no reviews yet.