MEMOPOWER-Ⅲ UPS
MEMOPOWER-Ⅲ 1-3kVA online UPS has lots of fans due to its reliability(online double conversion, PF:0.99) and compact size(A4 size). Thanks to the new Battery Discharge protection control function, it’s perfect for medium voltage substation applications. You can also choose PF:0.8 or PF:1.0 for your case.
General Features
● Online double conversion
● High power density
● Online double conversion with full digital control
● Wide input voltage range:110~300Vac
● Input power factor 0.99 with PFC
● Selectable output voltage: 208/220/230/240Vac
● Smart charger design for optimized battery performance
● Maximum charging current can be expanded to 12A (Long run unit)
● Emergency power off function (EPO)
● ECO mode operation for energy saving
● Generator compatible
● Cold start
● Intelligent fan speed regulation
● Load segment settable (Optional)
● Versatile LCD human-computer interface
● Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
● Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm
Technical Specification
Model MP 2k S
Capacity 2000VA/ 1800W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range – 110~300Vac (176~280Vac @ 100% load)
Frequency range – 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output Line Mode 46~54Hz or 56~64Hz
frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤3% Linear load
≤5% Non linear load
Transfer time
AC mode to Bat.Mode 0ms
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 90%
Battery mode 87%
BATTERY
Battery number 4
Capacity (Standard unit) 9Ah/12V
Typical recharging time is 4 hours (to 90% of full capacity)
Charging voltage 82.2Vdc±1%
Charging current (Max) 1A
INDICATORS
LED display Line mode,Bat. mode,ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage,
Battery voltage, Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continuously beeping
PHYSICAL
Dimension W x D×H (mm) 191 x 460 x 337
Net weight (kg) 19.5
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m, derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When the output voltage is 208Vac, needs to derate to 80% of the unit capacity.
Warranty 2 Years / 1 Year Battery
Reviews