Kstar MODEL MP 10k S 10KVA / 9000W Online double conversion Single Phase

79,000.00

Category: Tags: , , , , , , , , , ,

Description

MEMOPOWER Plus II

6-10kVA
 

MEMOPOWER-Ⅲ 6-10KVA

6kVA-10kVA

MEMOPOWER-Ⅲ 6-10kVA is new generation small power UPS of KSTAR, both input and output are single phase, the output factor is 0.9.The efficiengy of this UPS is very high,it can achieve power saving and reduce cost of customer in result.
General Features• Online double conversion with full digital control
• Optimization battery group, the quantity of battery: 16/18/20pcs (Settable)
• Wide input voltage range:110~286Vac
• Input power factor 0.99 with PFC
• Wide input frequency range
• Selectable output voltage: 208/220/230/240Vac
• Generator compatible
• ECO mode operation for energy saving
• Self-testing when UPS startup
• Multiple communication interface:RS232/USB/EPO(Relay card /SNMP card optional)
• Cold start
• Design with maintenance switch (Optional)
• Intelligent fan speed regulation
• Multiple protection function:short-circuit,overload,overheat, battery overcharge and overdischarge,output low voltage and fan fault alarm

Technical Specification

MODEL MP 10k S
Capacity 10000VA/ 9000W
NPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Bypass voltage range Max.voltage:230~264Vac
Min.voltage:176~220Vac
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output frequency Line Mode ±10% of the rated frequency
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THDv) ≤2% Linear load
≤5% Non linear load

Transfer time
AC mode to Bat.Mode 0ms
Inverter to Bypass 5ms (Typical)
utput waveform Pure Sinewave

Overload
Line Mode Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately
Bypass Mode 63A (Breaker)
Efficiency 93.50%

Battery voltage
Battery voltage 240Vdc

Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 8A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
Battery voltage,Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337 ; S:191 x 460 x 720 (With wheel)
Net weight (kg) 71

ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m

Noise level <58db at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Reviews