Description
Master II Series (3P/3P)
PRO83300-QS/QL SERIES 10-80KVA
Master II Series (3P/3P)-Tower
PROLiNK Master II Series (3P/3P) Tower Type is a three-phase output UPS system that employs a true online double-conversion technology. A Digital Signal Processor (DSP) technology digitizes the data and mathematically manipulates them to provide an improved solution with higher performance and reliability.
GENERAL
UPS Type | Tower |
Phase | 3-phase in / 3-phase out |
Rating (VA) | 30000VA |
Nominal Power (W) | 30000W |
Standard ModelDimension (mm) | 815 x 300 x 1000 (D x W x H) |
Weight (kg) | 225 |
Long-run ModelDimension (mm) | 815 x 300 x 1000 (D x W x H) |
Weight (kg) | 60 |
INPUT
Nominal Voltage | 3 x 400 VAC (3Ph+N) |
Voltage Range | 190-520 VAC (3-phase) @ 50% load305-478 VAC (3-phase) @ 100% load |
Frequency Range | 46~54 Hz or 56~64Hz |
Power Factor | ≧0.99 @ 100% Load |
OUTPUT
Output Voltage | 3 x 360*/380/400/415 VAC (3Ph+N) |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦2% THD (Linear load)≦5% THD (Non-linear load) |
ALARM & INDICATORS
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
MANAGEMENT
Smart RS-232 / USB | Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac |
Optional SNMP | Power management from SNMP manager and web browser |
BATTERY
Standard ModelType | 12V Lead Acid |
Numbers | (16+16)pcs x 2 strings |
Typical Recharge Time | 4 hours recover to 90% capacity |
Long-run ModelType | Depending on customer |
Numbers | (16+16) or (18+18) or (20+20)pcs |
Charging Current (max) | 1~12A Adjustable |
REAR PANEL
1. RS-232 communication port
2. USB communication port
3. Emergency power off function connector (EPO connector)
4. Share current port*
5. Parallel port**
6. Intelligent slot
7. External battery connector/terminal*** (for both standard and long run models)
8. Line input circuit breaker/switch
9. Maintenance bypass switch
10. Bypass input circuit breaker/switch
11. Output circuit breaker/switch
12. Line input terminal
13. Bypass input terminal
14. Output terminal