Vertiv Liebert GXT5-16KIRT9UXLN On-Line 16kVA/16kW 230V LCD 9U Rack/Tower, Rail Kit Bundled

567,900.00

Description

Liebert GXT5 750VA – 20kVA

Vertiv™ Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers robust power outage protection and continuous power conditioning in a compact and flexible deployment system. Liebert GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications. Liebert GXT5 comes with various models ranging from 750VA to 20kVA and in both tower or rack form factor.

                 Get Brochure             

Best Suited For:
  • Banking, Financial and Insurance
  • Data Center/Colocation/Hosting
  • Education
  • Government
  • Healthcare
  • Manufacturing
  • Retail and Wholesale
  • Telecom
  • Transportation

Warranty: 3 Years Warranty

 

Technical Specifications

Ratings (VA/W) 16000 VA/16000 W

Dimensions, inches (mm) UnitWxDXH 16.9×24.8×15.5 (430×630×394)

Weight, pounds (kg) Unit 298 (135.2)

Input AC Parameters

Operating Frequency, Nom 50 or 60 Hz (Factory Default is 50 Hz )

Input Voltage 200/208/220/230/240 VAC Single Phase+ neutral + PE (or) 345/360/380/400/415 VAC Three phase + neutral + PE

Operating Voltage Range Without Battery Operation (VL-N)

176 to 288 VAC (100 to 176 VAC with power derating)

Input Frequency Without Battery Operation 40 to 70 Hz

 

Output AC Parameters

AC-AC Efficiency Up to 95.9%

User-configurable Voltage 200/208/220/230/240 VAC

Factory Default Voltage 230V

Frequency 50 Hz

Waveform Pure Sinewave

Main Mode Overload ≤ 105% continuous ; 105 to 125% for 5 minutes; 125 to 150% for 60 seconds; > 150% minimum 200 ms

Internal Battery

Charger Current 2.25 A (default), maximum 13 A

Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 32x 12V x 9.0 AH

Back-up Time at Full Load 3.5 Min.

Back-up Time at Half Load 9.5 Min

Bypass Protection Limits

Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.

Lower -limit Selections – 10% – 15% -20%; default – 15%

Disable-bypass operation When the input frequency prevents synchronous operation

General

Operating Temperature Full power up to 40 oC (up to 50 oC with derating)

Storage Temperature -20 to +60 °C ( contain batteries will be from -15 to 40 °C)

Relative Humidity 0 to 955 non-condensing

Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating

Audible Nose <58 dBA

Safety

UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013

EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A), CISPR22 Class A (RFI)

ESD IEC/EN EN61000-4-2, Level 4, Criteria B

Radiated Susceptibility IEC/EN EN61000-4-3, Level, Criteria A

Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria B

Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B

Transportation ISTA Procedure 1E

POD

Model Number PD5-CE10HDWRMBS

Amp Rating 63 A

Includes Four ICE320 C19 16 A / 250 V Sockets, Four C13 10 A / 250 V Sockets

 

Features

Available in 750VA/1/1.5/2/3/5/6/8/10/16/20kVA
Top-level on-line double conversion UPS for mission-critical application
Unity output power factor
LCD multi-language color display (gravity sensing)
On-line (VFI) mode efficiency up to 95.9% at full load
Active ECO mode efficiency up to 99%
Energy Star 2.0 certified
Controllable and programmable output sockets
Integrated solution with batteries and electronics
External battery cabinets auto-detection
Operates at full power up to 40°C (up to 50°C with derating)
Intelligent Communication ready
Safety Agency Approved Category B IEC 61000-4-5 Surges/Lightning protection capability