Vertiv™ Liebert® ITA2 40KVA/40KW UPS 400V LCD long backup model

661,500.00

Remarkable Efficiency and Flexibility characterize the
Liebert® ITA2 UPS
Featuring true online double conversion technology, unity
power factor and an extremely compact rack-tower design,
Liebert ITA2 is the perfect power protection solution for your
computer rooms, storage, and network equipment.

Description

Description
With a unity output power factor, Liebert
ITA2 perfectly matches the needs of
modern IT loads, and with its wide input
voltage and frequency range it effectively
reduces the need for battery intervention,
thus prolonging battery life.
It is also endowed with intelligent fans with
automatic speed control, which effectively
save energy and reduce noise.
Liebert ITA2 supports common battery
configurations between paralleled UPS
and the number of batteries per string,
which can be arranged flexibly, facilitating
the utilization of different battery systems
and saving on battery investment.
An extra powerful battery charger
across all models capable of recharging
high capacity battery strings ensure a
fast charge-restoration even after a
prolonged power outages.
Liebert ITA2 offers enhanced flexibility
with a wide range of accessories for
both stand-alone and rack-mount
installations. When rack mounted,
it allows to installation of up to 40 kVA UPS
in just 3 U of space, achieving a
remarkable space saving. Parallelability
and maintenance are facilitated through
the use of dedicated maintenance
bypass option while extending the backup
time can be provided with matching
battery modules (10-20 kVA) for a neat
rack-mounted installation.
Liebert ITA2 features a multi-lingual
LCD user interface allows close
control and monitoring of the system
status and performance.

 

 

Input
Nominal input voltage (V): 380/400/415 (Line voltage)
Input voltage range without
battery discharge (V):
176 ~ 288, at full load
100Vac ~ 176Vac, linear derating
100Vac, at half load
Nominal input frequency (Hz) 50/60
Input frequency range (Hz) 40 ~ 70
Bypass voltage tolerance (%):
Upper limit: +10%, +15% or +20%;
default: +20%; Lower limit: -10%, -20%,
-30% or -40%; default: -40%
Bypass frequency tolerance (%) ±5Hz, ±10Hz
Input power factor at full load (kW/kVA) ≥0.99, at full load; ≥0.98, at half load
Current THD at full linear load (THDI%) <3% (for linear full load)
Battery Management
Battery blocks per string 32-40**
Voltage temperature compensation
(mV/°C/Cell) default 3 mV/cell/, can be set to 0~5mV/
cell/ from Paramset
Battery charger max. current (A) ≤ 13A
Output
Nominal output voltage (V) 380/400/415 (three-phase)
Nominal output frequency (Hz) 50/60
Maximum active power (kW) 40
THDv at full linear load (%):
< 2% (linear load);
< 5% (non-linear load)
Inverter overload capacity at 25°C
Up to 105% continuous
105%-125% for 10 min
125%-150% for 1 min
> 150%, 200 ms
Efficiency
Double conversion efficiency 96.6%
ECO Mode Efficiency 99%
Dimensions and Weight
Dimensions (W x D x H) (mm):
430 x 590 x 130 (3U) ***
430 x 730 x 173 (4U) (single POD)
430 x 730 x 261 (6U)
(1+1 parallel POD)
Net Weight (kg):
30/52 (UPS)
20/30 (Single POD)
28/43 (1+1 Parallel POD)
General
Noise at 1 m (dBA) 63
Ventilation Front to back
Maximum altitude 1500 m without derating (max. 3000 m)
Protection level IEC (60529) IP20
General and safety requirements for UPS EN/IEC/AS/BS 62040-4
EMC requirements for UPS EN/IEC/AS/BS 62040-2
UPS classification according to
CEI EN 62040-3 VFI-SS-111
Environmental aspects EN/IEC/BS 62040-4